Low-pressure appliances: centrifugal chillers running at 30 psig or lower at a 104°F liquid-phase temperature. A system below atmospheric pressure pulls air and moisture in through any leak — that changes everything about how you work on it.
Low-pressure chiller shut down for the season. The tech leaves the system under vacuum.
The call: Bring it slightly above atmospheric pressure — an idled low-pressure system left under vacuum pulls air and moisture in.
A low-pressure system operates below atmospheric pressure, so air and moisture enter through any leak path. Maintaining pressure slightly above atmospheric keeps air out.
Low-pressure chiller, purge unit running excessively. The tech assumes the purge unit is doing its job.
The call: The purge unit is telling you the system leaks — excessive running generally indicates a leaking system.
The purge unit removes non-condensables, taking suction from the top of the condenser and sending refrigerant back to the evaporator. High head pressure is another sign of air in the system. And nitrogen leak testing on that chiller maxes out at 10 psig.
Type III is the smallest Type section — 6 topics, 13 calls — but it is the one most techs never touch in the field, which is exactly why the exam tests it.