Home / EPA 608 Practice Test / Type II
31 callswork-order decisions
15 topicscovered in this section
25 questionson the real Type II exam
18 of 2570% to pass
What Type II covers
- System Classifications
- Determining System Charge
- Leak Repair Requirements
- Leak Repair Time Frames
- Section 608 Leak Repair Regulations (Inspection Frequency)
- Record Keeping
- Leak Detection
- Recovery Techniques: Before You Recover
- Recovery and Service Techniques: Enhancing the Process
- Recovery Techniques: Required Evacuation Levels
- Refrigeration System Liquid-Line Accessories
- Refrigeration System Suction Line and Compressor Accessories
- System Evacuation
- System Charging and the Temperature-Pressure Chart
- Refrigerant Leak Detectors
Key numbers to know
- Leak repair is triggered at 10% of charge per year for comfort cooling, 20% for commercial refrigeration, 30% for industrial process refrigeration.
- The repair rules apply at 50 lbs of charge or more. The owner has 30 days to repair once the threshold is exceeded.
- A system with 200 lbs or more that passes its initial verification test gets a follow-up verification test within 10 days.
- Before a major repair on an R-410A system over 200 lbs, recover to at least 10 inches of mercury vacuum.
- A deep vacuum of 500 microns is the target before charging any system.
- If leaks make the prescribed recovery level unattainable, recover to atmospheric pressure (0 psig) — the chart does not apply to a system that cannot hold a vacuum.
Try two calls
Work-order call · Type II · System classifications
Which leak rate applies?
A system cools both a factory floor and the offices above it. The owner asks which leak rate category applies.
The call: The category with the highest percentage of use.
If the process side dominates, it's Industrial Process Refrigeration at 30%. If comfort cooling dominates, it's 10%. The percentage decides, not the building type.
Work-order call · Type II · System classifications
It's a car AC, Type II covers it
The tech is asked to service a motor vehicle air-conditioning system with a Type II certification.
The call: No — MVAC is its own category and is not covered by Type II.
Type II covers high- and very high-pressure appliances except small appliances and MVAC systems.
Type II is the biggest section — 15 topics, 31 calls — because it is where most working techs live. The leak-rate numbers and the recovery levels are the ones to know cold.
Work all 31 Type II calls
Five calls free across the whole practice, no email. The $39 pass opens every call and the 100-question practice exam.
Start free — 5 calls See the practice test
First 5 work-order calls free, no email. $39 pass unlocks all 96 calls and the 100-question practice exam. Live until you pass, up to one year. Checkout opens at launch — preview unlock is on for review.